Električni tok za NYY, NAYY, NYCY, NYCWY

Električni tok NYY, NAYY, NYCY, NYCWY 0,6/1 kV
Current ratings for NYY, NAYY, NYCY, NYCWY 0,6/1 kV
  
Električni tok v Amperih (A), Polaganje v zemljo (20°C)/ Current carrying capacity in Ampere (A), laying in ground (20°C)

Nominalni presek
Nominal Cross-section
mm²
Bakreni vodnik
Copper conductor
Aluminijski vodnik
Aluminium conductor
NYY NYWCY NAYY NAYCWY
1,5 30 27 41 31 27
2,5 39 36 55 40 36
4 50 47 71 51 47
6 62 59 90 63 59
10 83 79 124 84 79
16 107 102 160 108 102
25 138 133 208 139 133 106 102 160 108 103
35 164 159 250 166 160 127 123 193 129 123
50 195 188 296 196 190 151 144 230 153 145
70 238 232 365 238 234 185 179 283 187 180
95 286 280 438 281 280 222 215 340 223 216
120 325 318 501 315 319 253 245 389 252 246
150 365 359 563 347 357 284 275 436 280 276
185 413 406 639 385 402 322 313 496 314 313
240 479 473 746 432 463 375 364 578 358 362
300 541 535 848 473 518 425 419 656 397 415
400 614 613 975 521 579 487 484 756 441 474
500 693 687 1125 574 624 558 553 873 489 528
630 777 1304 636 635 1011 539
800 859 1507 716 1166
1000 936 1715 796 1332