Električni tok NYY, NAYY, NYCY, NYCWY 0,6/1 kV
Current ratings for NYY, NAYY, NYCY, NYCWY 0,6/1 kV
Električni tok v Amperih (A), Polaganje v zemljo (20°C)/ Current carrying capacity in Ampere (A), laying in ground (20°C)
Nominalni presek Nominal Cross-section mm² |
Bakreni vodnik Copper conductor |
Aluminijski vodnik Aluminium conductor |
||||||||
NYY | NYWCY | NAYY | NAYCWY | |||||||
1,5 | 30 | 27 | 41 | 31 | 27 | – | – | – | – | – |
2,5 | 39 | 36 | 55 | 40 | 36 | – | – | – | – | – |
4 | 50 | 47 | 71 | 51 | 47 | – | – | – | – | – |
6 | 62 | 59 | 90 | 63 | 59 | – | – | – | – | – |
10 | 83 | 79 | 124 | 84 | 79 | – | – | – | – | – |
16 | 107 | 102 | 160 | 108 | 102 | – | – | – | – | – |
25 | 138 | 133 | 208 | 139 | 133 | 106 | 102 | 160 | 108 | 103 |
35 | 164 | 159 | 250 | 166 | 160 | 127 | 123 | 193 | 129 | 123 |
50 | 195 | 188 | 296 | 196 | 190 | 151 | 144 | 230 | 153 | 145 |
70 | 238 | 232 | 365 | 238 | 234 | 185 | 179 | 283 | 187 | 180 |
95 | 286 | 280 | 438 | 281 | 280 | 222 | 215 | 340 | 223 | 216 |
120 | 325 | 318 | 501 | 315 | 319 | 253 | 245 | 389 | 252 | 246 |
150 | 365 | 359 | 563 | 347 | 357 | 284 | 275 | 436 | 280 | 276 |
185 | 413 | 406 | 639 | 385 | 402 | 322 | 313 | 496 | 314 | 313 |
240 | 479 | 473 | 746 | 432 | 463 | 375 | 364 | 578 | 358 | 362 |
300 | 541 | 535 | 848 | 473 | 518 | 425 | 419 | 656 | 397 | 415 |
400 | 614 | 613 | 975 | 521 | 579 | 487 | 484 | 756 | 441 | 474 |
500 | 693 | 687 | 1125 | 574 | 624 | 558 | 553 | 873 | 489 | 528 |
630 | 777 | – | 1304 | 636 | – | 635 | – | 1011 | 539 | – |
800 | 859 | – | 1507 | – | – | 716 | – | 1166 | – | – |
1000 | 936 | – | 1715 | – | – | 796 | – | 1332 | – | – |